Weintek cMT3092X

July 23, 2026

Weintek cMT3092X
All CISA Advisories, CISA, July 23, 2026

View CSAF

Summary

Successful exploitation of these vulnerabilities could allow a non-privileged user to escalate privileges or view the credentials of other users.

The following versions of Weintek cMT3092X are affected:

  • cMT3092X firmware <20210218 
  • EasyWeb <v2.1.20
CVSS Vendor Equipment Vulnerabilities
v3 8.8 Weintek Weintek cMT3092X Reliance on Cookies without Validation and Integrity Checking in a Security Decision, Incorrect Permission Assignment for Critical Resource, Plaintext Storage of a Password, Incorrect User Management

Background

  • Critical Infrastructure Sectors: Critical Manufacturing
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: Taiwan

Vulnerabilities

Expand All +

CVE-2026-60134

Weintek cMT3092X HMI allows a non-privileged user to modify cookies to gain elevated privileges.

View CVE Details


Affected Products

Weintek cMT3092X
Vendor:
Weintek
Product Version:
Weintek cMT3092X firmware: <20210218, Weintek EasyWeb: <v2.1.20
Product Status:
known_affected
Remediations

Vendor fix
Weintek recommends users apply the patch package named cmt_typeB_20260316_007.patch, which contains a newer EasyWeb 2.3.17-typeb. This fix will be delivered as a patch-only update; no separate standard firmware release is planned. Users may request the patch directly from Weintek support (https://www.weintek.com/globalw/Support/Knowledge.aspx) or from distributors.
https://www.weintek.com/globalw/Support/Knowledge.aspx

Mitigation
Weintek has published a document with more details about this issue at https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf.
https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf

Relevant CWE: CWE-784 Reliance on Cookies without Validation and Integrity Checking in a Security Decision


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 8.7 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CVE-2026-61892

Weintek cMT3092X HMI allows a non-privileged user to modify tokens to escalate privileges.

View CVE Details


Affected Products

Weintek cMT3092X
Vendor:
Weintek
Product Version:
Weintek cMT3092X firmware: <20210218, Weintek EasyWeb: <v2.1.20
Product Status:
known_affected
Remediations

Vendor fix
Weintek recommends users apply the patch package named cmt_typeB_20260316_007.patch, which contains a newer EasyWeb 2.3.17-typeb. This fix will be delivered as a patch-only update; no separate standard firmware release is planned. Users may request the patch directly from Weintek support (https://www.weintek.com/globalw/Support/Knowledge.aspx) or from distributors.
https://www.weintek.com/globalw/Support/Knowledge.aspx

Mitigation
Weintek has published a document with more details about this issue at https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf.
https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf

Relevant CWE: CWE-732 Incorrect Permission Assignment for Critical Resource


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 8.7 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CVE-2026-61886

Weintek cMT3092X HMI stores user account passwords in plaintext.

View CVE Details


Affected Products

Weintek cMT3092X
Vendor:
Weintek
Product Version:
Weintek cMT3092X firmware: <20210218, Weintek EasyWeb: <v2.1.20
Product Status:
known_affected
Remediations

Vendor fix
Weintek recommends users apply the patch package named cmt_typeB_20260316_007.patch, which contains a newer EasyWeb 2.3.17-typeb. This fix will be delivered as a patch-only update; no separate standard firmware release is planned. Users may request the patch directly from Weintek support (https://www.weintek.com/globalw/Support/Knowledge.aspx) or from distributors.
https://www.weintek.com/globalw/Support/Knowledge.aspx

Mitigation
Weintek has published a document with more details about this issue at https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf.
https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf

Relevant CWE: CWE-256 Plaintext Storage of a Password


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
4.0 7.1 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N

CVE-2026-60135

An attacker can modify data that should be restricted to read‑only access.

View CVE Details


Affected Products

Weintek cMT3092X
Vendor:
Weintek
Product Version:
Weintek cMT3092X firmware: <20210218, Weintek EasyWeb: <v2.1.20
Product Status:
known_affected
Remediations

Vendor fix
Weintek recommends users apply the patch package named cmt_typeB_20260316_007.patch, which contains a newer EasyWeb 2.3.17-typeb. This fix will be delivered as a patch-only update; no separate standard firmware release is planned. Users may request the patch directly from Weintek support (https://www.weintek.com/globalw/Support/Knowledge.aspx) or from distributors.
https://www.weintek.com/globalw/Support/Knowledge.aspx

Mitigation
Weintek has published a document with more details about this issue at https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf.
https://dl.weintek.com/public/Document/TEC/TEC25003E_cMT_EasyWeb_V2_Security_Issues.pdf

Relevant CWE: CWE-286 Incorrect User Management


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N
4.0 7.1 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N

Acknowledgments

  • Vincenzo Giuseppe Colacino of Secoore reported these vulnerabilities to CISA

Legal Notice and Terms of Use

This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).


Recommended Practices

CISA recommends users take the following measures to protect themselves from social engineering attacks:

Practice principles of least privilege.

Do not click web links or open attachments in unsolicited email messages.

Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.

Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.


Revision History

  • Initial Release Date: 2026-07-23
Date Revision Summary
2026-07-23 1 Initial Publication

Legal Notice and Terms of Use