Rockwell Automation 1756-ENBT Module

September 3, 2026

Rockwell Automation 1756-ENBT Module
All CISA Advisories, CISA, September 3, 2026

View CSAF

Summary

Successful exploitation of this vulnerability could crash the module. The device requires a restart to recover.

The following versions of Rockwell Automation 1756-ENBT Module are affected:

  • 1756-ENBT module vers:all/* (CVE-2025-10478)
CVSS Vendor Equipment Vulnerabilities
v3 7.5 Rockwell Automation Rockwell Automation 1756-ENBT Module Improper Check for Unusual or Exceptional Conditions

Background

  • Critical Infrastructure Sectors: Critical Manufacturing, Food and Agriculture, Transportation Systems, Water and Wastewater
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: United States

Vulnerabilities

Expand All +

CVE-2025-10478

A denial-of-service security issue exists in the Rockwell Automation 1756-ENBT module which is a ControlLogix EtherNet/IP bridge that enables communication between Logix 5000 controllers and Ethernet devices. An attacker could exploit this vulnerability by sending a crafted CIP packet, causing the module to crash. The device requires a restart to recover.

View CVE Details


Affected Products

Rockwell Automation 1756-ENBT Module
Vendor:
Rockwell Automation
Product Version:
Rockwell Automation 1756-ENBT module: vers:all/*
Product Status:
known_affected
Remediations

Mitigation
Rockwell Automation recommends that users upgrade to 1756-EN2T or 1756-EN4TR. Users who are not able to upgrade should use Rockwell Automation’s security best practices.
https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight

Mitigation
For more information on this issue, see the corresponding Rockwell Automation security advisory.
https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html

Relevant CWE: CWE-754 Improper Check for Unusual or Exceptional Conditions


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
4.0 8.7 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Acknowledgments

  • Rockwell Automation reported this vulnerability to CISA.

Legal Notice and Terms of Use

This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).


Recommended Practices

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.


Revision History

  • Initial Release Date: 2026-09-03
Date Revision Summary
2026-09-03 1 Initial Republication of Rockwell Automation security advisory.

Legal Notice and Terms of Use

Go to Top